A wire with aluminum conductor and PVC insulation

APPLICATION:

The wire is designed for electric plants and fixed installation in power lighting systems, as well as for fixed installation of electrical equipment of apparatuses, mechanisms and machines at rated voltage of up to 450 V (for 450/750 V networks) and frequency of up to 400 Hz or DC voltage of up to 1000 V.

CONSTRUCTION:

Conductor - Solid conductor made of flexible aluminum wire

If wire section is 25 mm2 or more, the conductor is of stranded type and 2 flexibility class

Insulation - Insulating PVC compound. Color - white, gray, yellow, orange, red, pink, blue, green, brown,

black, purple and yellow-green (for solid conductors of up to 6 mm2 in section).

OPERATION AND INSTALLATION CONDITIONS:

Installation in hollow ducts of building structures, mounting boxes, trays, pipes, as well as in bundles inside switchboards, control cabinets and control panels of equipment

Operation conditions - ambient temperature from -50°C to +70°C, relative humidity of up to 100% at the

temperature of up to +35°C

Installation temperature - not below -15°C

Allowable continuous temperature of conductors heating - 70°C max Installation bends - at least 10 diameters

Insulation is resistant to cracking at temperature of 150°C as well as to deformation at temperature of 70°C Service life under normal operating conditions - at least 15 years

ELECTRICAL CHARACTERISTICS:

Electric resistivity of conductor at temperature of 20°C, Ohm*mm2/m - 0.02800 max;

Insulation resistance at 20°C, MOhm/km - at least 1

PRIMARY MANUFACTURED ASSORTMENT

Type of APV

Number of conductors in wire

Diameter of conductor, mm

1

2,5; 4,0; 6,0; 10; 16; 25; 35; 50; 70

DELIVERY FORM:

Wire is delivered in coils or wooden drums as per GOST 5151-79, in lengths not shorter than construction ones.